29
gG fuses
uR or aR fuses
Type
ACQ580-01-
Min. short-
circuit
current
1)
Input
current
gG (IEC 60269)
Nominal
current
I
2
t Voltage
rating
ABB type IEC
60269
size
A A A A
2
s V
3-phase U
N
= 230 V
089A-2 1300 89.0 125.0 103000 500 OFAF00H125 00
115A-2 1300 115 .0 125.0 103000 500 OFAF00H125 00
3-phase U
N
= 400 or 480 V
088A-4 1000 88 100 65000 500 OFAF000H100 000
106A-4 1300 106 125 103000 500 OFAF00H125 00
3AXD00000586715.xls L
1)
Minimum short-circuit current of the installation
Type
ACQ580
-01-
Min. short-
circuit
current
1)
Input
current
uR or aR (DIN 43620 blade style)
Nominal
current
I
2
t Voltage
rating
Bussmann
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 230 V
089A-2 700.0 89.0 200.0 15000.0 690 170M3815 1
115A-2 700.0 115.0 200.0 15000.0 690 170M3815 1
3-phase U
N
= 400 or 480 V
088A-4 700 88 160 16000 690 170M1569 000
106A-4 1280 106 315 46500 690 170M3817 1
3AXD00000586715.xls L
1)
Minimum short-circuit current of the installation
Type
ACQ580
-01-
Min. short-
circuit
current
1)
Input
current
uR or aR (DIN 43653 bolted tags)
Nominal
current
I
2
t Voltage
rating
Bussmann
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 400 or 480 V
088A-4 700 88 160 16000 690 170M1319 000
106A-4 700 106 200 15000 690 170M3015 1
3AXD00000586715.xls L
1)
Minimum short-circuit current of the installation