EasyManua.ls Logo

ABB ACS 300 Series - Chapter 4 - Control Connections

ABB ACS 300 Series
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS 300 User’s Manual 9
Chapter 1 - Overview of This Manual
Figure 1-4 ACS 300 block diagram.
Control Panel
(option)
RS232
Adapter
(option)
+10Vref, max 10mA
GND
AI 0/4-20mA, 0/2-10V
GND
+24V, max 50mA
DI1
DI2
DI3
DI4
DI5
max +48Vdc
0: Uin < 3V
1: Uin>10V
AO, 0-20mA, R<500oh
m
RO1
RO2
max:
300Vdc
250Vac
2kVA switching
2Arms cont.
CONTROL BOARD
MAIN CIRCUIT
Galvanic Isolation
analogue input
configured by
X5
digital inputs
configured by
S1
A
B
C
I U
Control Block
* uC
* ROM
* RAM
* EEPROM
* modulator
Field Bus
Adapters
(option)
X10
X1X2
RFI
Filter
(option,
R0)
Line Chokes
(option,
R0, R1)
PE
L1(L1)
L2(N)
L3
RFI Filter
(R1, R2)
Line Choke
(R2)
Rectifier
Power
Supply
Precharge
Circuit
Brake
Chopper
(R0, R1)
BRAKE RES
I, U Feedback Gate control
Inverter
U2
V2
W2
Output Chokes
(option)
3~
Brake Unit
(option, R2)
Brake Resistor
(option, R0, R1, R2)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 181..6
GND
I U
250
200k
50k
6k8
8V2
27V
22k
PTC
UDC+
UDC-
PE
R191
10M
Fan (R1.R2 only)
DDCS
PE
PE