EasyManua.ls Logo

ABB ACS 501 - Start-Up Data Parameters

ABB ACS 501
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 – Start-up Procedure
ACS 501 Installation & Start-up Manual 4-3
Start-up Data
Parameters
Power up the ACS 501. The display shows Operating Data Parameter 1
(Output Frequency). Before proceeding with the start-up, check and complete
the Start-up Data Parameter values. Do not change parameters at this time
except as described in the following steps.
While viewing Parameter 1 (Output Frequency) press and hold [ * ], then
press [Right Arrow]. The display shows Parameter A (Language) in Setting
mode.
A LANGUAGE
Press [Up Arrow] or [Down Arrow] to select your preferred language. The
ACS 501 displays all information in the language you select. Press [ * ] to
confirm the selection and move to the next parameter. The available languages
are: English, German, Italian, Spanish, Dutch, French, Danish, Finnish, and
Swedish.
B APPLICATIONS
Leave this in the FACTORY setting to perform the start-up procedure. If
anything other than FACTORY displays, press [Up Arrow] or [Down Arrow]
to change the parameter to FACTORY. Press [ * ] to confirm the selection and
move to the next parameter.
C APPLIC. RESTORE
This parameter restores all parameters of the current application to factory-set
parameter values. Set this to YES by pressing [Up Arrow]. Press [ * ] to
confirm the selection and move to the next parameter.
D SUPPLY VOLTAGE
This parameter offers choices of 440, 460, 480, and 500 VAC for 480-volt
units; 380, 400, and 415 VAC for 380-volt units; or 208, 220, 230, and 240
VAC for 230-volt units.
Press [Up Arrow] or [Down Arrow] to select the voltage value which matches
the line voltage providing power to your ACS 501. Press [ * ] to confirm the
selection and move to the next parameter.
E USER DISPLAY
SCALE
This parameter is used to set the scaling factor for Operating Data Parameter 2
(Speed). When set to 0, the speed display will show RPM. When set to 100,
the speed display will show %. When set to any other value from 0 – 10000,
the display will show this value (minus slip unless slip compensation is ON)
when the output frequency is at the frequency set by Start-up Data Parameter I
(Motor Base Frequency).
Press [Up Arrow] or [Down Arrow] to set the desired value of the speed
display. Press [ * ] to confirm the selection and move to the next parameter.
F MOTOR CURRENT
-FLA
This parameter matches the ACS 501 to the rated motor current, adjustable
between 0 and 1000 amps. The drive uses this parameter for motor overload
protection and current (amperage) information displays.
Press [Up Arrow] or [Down Arrow] to select the current (amperage) value for
your motor. Press [ * ] to confirm the selection and move to the next
parameter.

Table of Contents