Chapter 5 – Fault Tracing
5-6 ACS 501 Installation & Start-up Manual
21 MOT CONT This fault is related to
components in the Motor
Control Card.
Remove power, wait one
minute, then restore power.
If the problem persists, call
ABB Technical Support.
Record the specific fault
code, you may be asked for
it.
22 PAR REST Parameter restoring error.
Parameter checksum does not
match.
Reset fault display (the
display is reset allowing the
scrolling of parameters, but
the fault is not reset).
Check all parameter settings
or restore the factor settings.
Remove power, wait one
minute, then restore power to
check that the fault has
disappeared.
23 UNDER V 2 DC bus voltage does not rise
over 93% of V
N
during five
seconds after connecting the
input power.
Check supply voltage.
Call ABB Technical Support.
24 GND FAULT Ground Fault has been detected
in the motor or motor wiring.
Check the motor and motor
wiring for grounds faults.
Fault Message Possible Cause Remedy

Table of Contents