ACS510 User’s Manual 151
Embedded Fieldbus
Feedback from the Drive – EFB
Pre-defined Feedback
Inputs to the controller (drive outputs) have pre-defined meanings established by the 
protocol. This feedback does not require drive configuration. The following table lists 
a sample of feedback data. For a complete listing, see input word/point/object 
listings in the technical data for the appropriate protocol starting on page 155. 
Note! With Modbus, any parameter can be accessed using the format: “4” followed 
by the parameter number.
Actual Value Scaling
The scaling of actual values can be protocol dependent. In general, for Actual 
Values, scale the feedback integer using the parameter’s resolution. (See "Complete 
Parameter List for ACS510" section for parameter resolutions.) For example:
Where parameters are in percent, the "Complete Parameter Descriptions" section 
specifies what parameter corresponds to 100%. In such cases, to convert from 
percent to engineering units, multiply by the value of the parameter that defines 
100% and divide by 100%.
Drive Parameter
Modbus
 
Protocol Reference
ABB DRV DCU PROFILE
0102 SPEED 40102
0103 OUTPUT FREQ  40103
0104 CURRENT 40104
0105 TORQUE 40105
0106 POWER 40106
0107 DC BUS VOLTAGE 40107
0109 OUTPUT VOLTAGE 40109
0301 FB CMD WORD1 – bit 0 (STOP) 40301 bit 0
0301 FB CMD WORD1 1 – bit 2 (REV) 40301 bit 2
0118 DI 1-3 STATUS – bit 0 (DI3) 40118
Feedback 
Integer
Parameter 
Resolution
(Feedback Integer) * (Parameter Resolution) = Scaled Value
1 0.1 mA 1 * 0.1 mA = 0.1 mA
10 0.1% 10 * 0.1% = 1%