64 ACS510 User’s Manual
Start-Up
Complete Parameter Descriptions
This section describes the actual signals and parameters for ACS510.
Some values vary depending on the drive software options. This is indicated by
“+N688:” or “+N689 in the table below. Refer to the type code on the drive namplate.
For example ACS510-01...+N688
Group 99: Start-up Data
This group defines special Start-up data required to:
Set up the drive.
Enter motor information.
Term Definition
Actual signal Signal measured or calculated by the drive. Can be monitored by the
user. No user setting possible.
FbEq Fieldbus equivalent: The scaling between the value shown on the panel
and the integer used in serial communication.
Parameter A user-adjustable operation instruction of the drive.
Code Description
9901 LANGUAGE
Selects the display language.
9902 APPLIC MACRO
Selects an application macro. Application macros automatically edit parameters to configure the ACS510 for a
particular application.
9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
Must equal the value on the motor rating plate.
The ACS510 cannot supply the motor with a voltage greater than the
mains voltage.
9906 MOTOR NOM CURR
Defines the nominal motor current.
Must equal the value on the motor rating plate.
Range allowed: (0.2…2.0) · I
2n
.
9907 MOTOR NOM FREQ
Defines the nominal motor frequency.
Range: 10…500 Hz,or 10...50 HZ (+N688), or 10...55 HZ (+N689).
Sets the frequency at which output voltage equals the
MOTOR NOM
VOLT.
Field weakening point = Nom Freq * Supply Volt / Mot Nom Volt
9908 MOTOR NOM SPEED
Defines the nominal motor speed.
Must equal the value on the motor rating plate.
0 = ENGLISH 1 = CHINESE 2 = KOREAN 3 = JAPANESE
1 = ABB STANDARD 2 = 3-WIRE 3 = ALTERNATE 4 = MOTOR POT 5 = HAND/AUTO
6 = PID CONTROL 7 = PFC CONTROL 15 = SPFC CONTROL
0 = USER S1 LOAD -1 = USER S1 SAVE -2 = USER S2 LOAD -3 = USER S2 SAVE
Output voltage
Output
P 9907
frequency
P 9905