230 ACS510 User’s Manual
Technical Data
Analog Cables
Recommendations for analog signal runs:
• Use double shielded, twisted pair cable.
• Use one individually shielded pair for each signal. 
• Do not use a common return for different analog signals.
Digital Cables
Recommendation for digital signal runs: A double shielded cable is the best 
alternative, but single-shielded, twisted, multi-pair cable is also usable. 
Control Panel Cable
If the control panel is connected to the drive with a cable, use only Category 5 Patch 
ethernet cable. The maximum length that is tested to meet EMC specifications is 3 m 
(9.8 ft). Longer cables are susceptible to electromagnetic noise and must be user- 
tested to verify that EMC requirements are met. Where long runs are required 
(especially for runs longer than about 12 m (40 ft)), use a RS232/RS485 converter at 
each end and run RS485 cable.
Drive’s Control Connection Terminals
The following table provides specifications for the drive’s control terminals
Efficiency
Approximately 98% at nominal power level.
Cooling
Air Flow, 380…480 V Drives
The following table lists heat loss and air flow data for 380…480 Volt drives.
Frame Size
Control
Maximum Wire Size  Torque
mm
2
AWG  Nm lb-ft
All 1.5 16 0.4 0.3
Cooling Specifications
Method Internal fan, flow direction from bottom to top. 
Requirement
Free space above and below the ACS510 drive: 200 mm (8 in).
Free space is not required on the drive’s sides – ACS510 drives can be mounted 
side-by-side.
Drive Heat Loss Air Flow
ACS510-01- Frame Size W 
BTU/hr m
3
/h  ft
3
/min
-03A3-4 R1 40
137 44 26
-04A1-4 R1 52 178 44 26