ACS510 User’s Manual 231
Technical Data
-05A6-4 R1 73 249 44 26
-07A2-4 R1 97
331 44 26
-09A4-4 R1 127
434 44 26
-012A-4 R1 172
587 44 26
-017A-4 R2 232 792 88 52
-025A-4 R2 337
1151 88 52
-031A-4 R3 457 1561 134 79
-038A-4 R3 562 1919 134 79
-046A-4 R3 667
2278 134 79
-060A-4 R4 907 3096 280 165
-072A-4 R4 1120 3825 280 165
-088A-4 R4 1440
4918 280 165
-125A-4 R5 1940 6625 350 205
-157A-4 R6 2310 7889 405 238
-180A-4 R6 2810
9597 405 238
-195A-4 R6 3050 10416 405 238
-246A-4 R6 3850 13148 540 318
-290A-4 R6 4550
15539 540 318
Drive Heat Loss Air Flow
ACS510-01- Frame Size W BTU/hr m
3
/h ft
3
/min
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn