ACS510 User’s Manual 63
Start-Up
NOTE: This parameter 1003 is not available in software option +N688 and +N689.
5314 EFB PAR 14 0…65535 1 0 (NOT SEL)
5315
EFB PAR 15 0…65535 1 0 (NOT SEL)
5316 EFB PAR 16 0…65535 1 0 (NOT SEL)
5317
EFB PAR 17 0…65535 1 0 (NOT SEL)
5318
EFB PAR 18 0...65535 1 0
5319 EFB PAR 19 0...0xFFFF (hex) 1 0
5320
EFB PAR 20 0...0xFFFF (hex) 1 0
Group 81: PFC Control
8103
REFERENCE STEP 1 0.0…100.0% 0.1% 0.0%
8104
REFERENCE STEP 2 0.0…100.0% 0.1% 0.0%
8105 REFERENCE STEP 3 0.0…1000.% 0.1% 0.0%
8109
START FREQ 1 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 50.0 Hz /
+N688:48.0 Hz /
+N689:53.0 Hz
8110
START FREQ 2 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 50.0 Hz /
+N688:48.0 Hz /
+N689:53.0 Hz
8111
START FREQ 3 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 50.0 Hz /
+N688:48.0 Hz /
+N689:53.0 Hz
8112
LOW FREQ 1 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 25.0 Hz /
+N688:25.0 Hz /
+N689:27.5Hz
8113
LOW FREQ 2 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 25.0 Hz /
+N688:25.0 Hz /
+N689:27.5Hz
8114
LOW FREQ 3 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 25.0 Hz /
+N688:25.0 Hz /
+N689:27.5Hz
8115
AUX MOT START D 0.0…3600.0 s 0.1 s 5.0 s
8116
AUX MOT STOP D 0.0…3600.0 s 0.1 s 3.0 s
8117 NR OF AUX MOT 0…6 1 1 9
8118
AUTOCHNG INTERV -0.1…336.0h 0.1h 0.0h (NOT SEL) 9
8119
AUTOCHNG LEVEL 0.0…100.0% 0.1% 50.0%
8120
INTERLOCKS 0…6 1 4 9
8121
REG BYPASS CTRL 0…1 1 0 (NO)
8122
PFC START DELAY 0.00…10.00 s 0.01 s 0.50 s
8123
PFC ENABLE 0…2 1 0 (NOT SEL) 9
8124
ACC IN AUX STOP 0.0...1800.0 s 0.1 s 0.0 s (NOT SEL)
8125
DEC IN AUX START 0.0...1800.0 s 0.1 s 0.0 s (NOT SEL)
8127
MOTORS 1…7 1 2
8128
AUX START ORDER
1…2 1 1
Group 98: Options
9802
COMM PROT SEL 0…4 1 0 (NOT SEL) 9
Code Name Range Resolution Default User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd