ACS510 User’s Manual 181
Fieldbus Adapter
Relay Output Control
Using the fieldbus for relay output control requires:
Drive parameter values set as defined below.
Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
1. More than 3 relays requires the addition of a relay extension module.
Note! Relay status feedback occurs without configuration as defined below.
Analog Output Control
Using the fieldbus for analog output control (e.g. PID setpoint) requires:
Drive parameter values set as defined below.
Fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1607 PARAM SAVE 1 (SAVE) Saves altered parameters to memory (then
value returns to 0).
Drive Parameter Value Description
Protocol
Reference
1401
RELAY OUTPUT 1 35 (COMM)
36 (
COMM(-1))
Relay Output 1 controlled by fieldbus.
1402
RELAY OUTPUT 2 Relay Output 2 controlled by fieldbus.
1403
RELAY OUTPUT 3 Relay Output 3 controlled by fieldbus.
1410
1
RELAY OUTPUT 4 Relay Output 4 controlled by fieldbus.
1411
1
RELAY OUTPUT 5 Relay Output 5 controlled by fieldbus.
1412
1
RELAY OUTPUT 6 Relay Output 6 controlled by fieldbus.
Drive Parameter Value Protocol Reference
0122
RO 1-3 STATUS Relay 1…3 status.
0123 RO 4-6 STATUS Relay 4…6 status.
Drive Parameter Value Description
Protocol
Reference
1501
AO1 CONTENT SEL 135 (COMM VALUE 1) Analog Output 1 controlled by
writing to parameter 0135.
0135
COMM VALUE 1–
1502
1505
AO1 CONTENT MIN
MAXIMUM AO1
Set appropriate
values.
Used for scaling
1506
FILTER AO1 Filter time constant for AO1.
1507
AO2 CONTENT SEL 136 (COMM VALUE 2) Analog Output 2 controlled by
writing to parameter 0136.
0136
COMM VALUE 2–
Drive Parameter Value Description
Protocol
Reference