198 ACS510 User’s Manual
Diagnostics
4 SHORT CIRC Fault current. Check for and correct:
A short-circuit in the motor cable(s) or motor.
Supply disturbances.
5
REVERSED Not used.
6 DC UNDERVOLT Intermediate circuit DC voltage is not sufficient. Check for and correct:
Missing phase in the input power supply.
Blown fuse.
Undervoltage on mains.
7
AI1 LOSS Analog input 1 loss. Analog input value is less than AI1FAULT LIMIT (3021).
Check for and correct:
Source and connection for analog input.
Parameter settings for
AI1FAULT LIMIT (3021) and 3001 AI<MIN FUNCTION.
8
AI2 LOSS Analog input 2 loss. Analog input value is less than AI2 FAULT LIMIT (3022).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI2 FAULT LIMIT (3022) and 3001 AI<MIN FUNCTION.
9 MOT OVERTEMP Motor is too hot, based on either the drive’s estimate or on temperature
feedback.
Check for overloaded motor.
Adjust the parameters used for the estimate (3005…3009).
Check the temperature sensors and Group 35 parameters.
10
PANEL LOSS Panel communication is lost and either:
Drive is in local control mode (the control panel displays LOC), or
Drive is in remote control mode (REM) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
Communication lines and connections
Parameter 3002
PANEL COMM ERR.
Parameters in Group 10: Command Inputs and Group 11: Reference
Select (if drive operation is REM).
11
REVERSED Not used.
12 MOTOR STALL Motor or process stall. Motor is operating in the stall region. Check for and
correct:
Excessive load.
Insufficient motor power.
Parameters 3010…3012.
13
RESERVED Not used.
14
EXT FAULT 1 Digital input defined to report first external fault is active. See parameter
3003
EXTERNAL FAULT 1.
15 EXT FAULT 2 Digital input defined to report second external fault is active. See parameter
3004
EXTERNAL FAULT 2.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action