200 ACS510 User’s Manual
Diagnostics
Faults that indicate conflicts in the parameter settings are listed below.
35 OUTPUT WIRING Possible power wiring error detected. When the drive is not running it
monitors for an improper connection between the drive input power and the
drive output. Check for and correct:
• Proper input wiring – line voltage is NOT connected to drive output.
• The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023
WIRING FAULT.
36 INCOMPATIBLE
SW
The drive cannot use the software.
• Internal Fault.
• The loaded software is not compatible with the drive.
• Call support representative.
37
CB OVERTEMP Drive control board is overheated. The fault trip limit is 88 °C. Check for and
correct:
• Excessive ambient temperature.
• Fan failure.
• Obstructions in the air flow.
Not for drives with an OMIO control board.
38
USER LOAD
CURVE
Condition defined by parameter 3701 USER LOAD C MODE has been valid
longer than the time defined by 3703
USER LOAD C TIME.
101...
199
SYSTEM ERROR Error internal to the drive. Contact your local ABB representative and report
the error number.
201…
299
SYSTEM ERROR Error in the system. Contact your local ABB representative and report the
error number.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action
1000
PAR HZRPM Parameter values are inconsistent. Check for any of the following:
• 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ.
• 2007
MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range
(> 50)
• 2008
MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range
(> 50)
1001
PAR PFC REF
NEG
Parameter values are inconsistent. Check for the following:
• 2007
MINIMUM FREQ is negative, when 8123 PFC ENABLE is active.
1003 PAR AI SCALE Parameter values are inconsistent. Check for any of the following:
• 1301
AI1 MIN > 1302 AI1 MAX.
• 1304
AI2 MIN > 1305 AI2 MAX.
1004 PAR AO SCALE Parameter values are inconsistent. Check for any of the following:
• 1504
AO1 MIN > 1505 AO1 MAX.
• 1510
AO2 MIN > 1511 AO2 MAX.
1005 PAR PCU 2 Parameter values for power control are inconsistent: Improper motor
nominal kVA or motor nominal power. Check for the following:
• 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / P
N
) < 3.0
• where: P
N
= 1000 * 9909 MOTOR NOM POWER (if units are kW)
or P
N
= 746 * 9909 MOTOR NOM POWER (if units are HP, e.g. in US)
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn