EasyManua.ls Logo

ABB ACS510-01 - Page 21

ABB ACS510-01
247 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS51
0
User’s Manual 21
Installation
Wiring IP54 Enclosure with Cables
1. Cut the cable seals as needed for the power,
motor, and control cables. (The cable seals are
cone-shaped, rubber seals on the bottom of the
drive.)
2. On the input power cable, strip the sheathing back
far enough to route individual wires.
3. On the motor cable, strip the sheathing back far
enough to expose the copper wire screen so that
the screen can be twisted into a pig-tail. Keep the
pig-tail short to minimize noise radiation.
360
o
grounding under the clamp is recommended
for the motor cable to minimize noise radiation. In
this case, remove the sheathing at the cable
clamp.
4. Route both cables through the clamps and tighten
the clamps.
5. Strip and connect the power/motor wires, and the power ground wire to the drive
terminals.
Note! For R5 frame size, the minimum power cable size is 25 mm
2
(4 AWG).
For R6 frame size, refer to "Power Terminal Considerations – R6 Frame Size" on
page 218.
1
IP5003
4
5
2
IP5004
3
4
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn