ACS510 User’s Manual 215
Technical Data
Fuses, 380…480 V Drives
Emergency Stop Devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
Generate an emergency stop of the motor.
Separate the drive from dangerous potential.
Input Power Cables/ Wiring
Input wiring can be any of:
A four conductor cable (three phases and ground/protective earth). Shielding is
not required.
Four insulated conductors routed through conduit.
Size wiring according to local safety regulations, appropriate input voltage and the
drive’s load current. In any case, the conductor must be less than the maximum limit
defined by the terminal size (see "Drive’s Power Connection Terminals" on page
218).
ACS510-01-
see below
Input Current
A
Input power (mains) fuses
IEC 269 gG (A)
UL Class T (A) Bussmann Type
-03A3-4 3.3 10
10 JJS-10
-04A1-4 4.1
-05A6-4 5.6
-07A2-4 7.2
-09A4-4 9.4
15 JJS-15
-012A-4 11.9 16
-017A-4 17
20 JJS-20
-025A-4 25 25
30 JJS-30
-031A-4 31 35
40 JJS-40
-038A-4 38 50
50 JJS-50
-046A-4 46
60 JJS-60
-060A-4 60 63
80 JJS-80
-072A-4 72 80
90 JJS-90
-088A-4 88 125
125 JJS-125
-125A-4 125 160
175 JJS-175
-157A-4 157 200
200 JJS-200
-180A-4 180 250
250 JJS-250
-195A-4 205 250
250 JJS-250
-246A-4 245 250
250 JJS-250
-290A-4 290 315
315 JJS-350