ACS510 User’s Manual 51
Start-Up
Macro Default Values for Parameters
Parameter default values are listed in "Complete Parameter List for ACS510".
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
ACS510-01
* This parameter is not available in software option +N688 and +N689.
Parameter
ABB
Standard
3-wire
Alternate
Motor
Potentiometer
Hand-auto
PID Control
PFC Control
SPFC Control
9902 APPLIC MACRO 123456715
1001
EXT1 COMMANDS 24922111
1002 EXT2 COMMANDS 00007666
1003
*
DIRECTION
33333111
1102
EXT1/EXT2 SEL 00003233
1103 REF1 SELECT 111121111
1106 REF2 SELECT 22222191919
1201
CONST SPEED SEL 910950900
1304 MINIMUM AI2 0 0 0 020202020
1401 RELAY OUTPUT 1 11111122
1402
RELAY OUTPUT 2 222222331
1403 RELAY OUTPUT 3 3333333131
1501 AO1 CONTENT SEL 103 102 102 102 102 102 103 103
1503
AO1 CONTENT MAX 50 50 50 50 50 50 52 52
1507 AO2 CONTENT SEL 104 104 104 104 104 104 130 130
1510 MINIMUM AO2 00000044
1601
RUN ENABLE 00664522
2008 MAXIMUM FREQ 50 50 50 50 50 50 52 52
2201 ACC/DEC 1/2 SEL 50500000
3201
SUPERV 1 PARAM 103 102 102 102 102 102 103 103
3401 SIGNAL 1 PARAM 103 102 102 102 102 102 103 103
4001 GAIN 2.5 2.5 2.5 2.5 2.5 2.5 25 2.5
4002
INTEGRATION TIME 33333333
4101 GAIN 1111112,52.5
4102
INTEGRATION TIME 60 60 60 60 60 60 3 3
8118
AUTOCHG INTERV 00000000.1
8123 PFC ENABLE 00000012