ACS550 User’s Manual 125
Start-Up
4016 ACT1 INPUT
Defines the source for actual value 1 (ACT1).
0 = AI 1 – Uses analog input 1 for ACT1.
1 = AI 2 – Uses analog input 2 for ACT1.
2 = Current – Uses current for ACT1, scaled so:
•Min ACT1 = 0 current
•Max ACT1 = 2 x nominal current
3 = Torque – Uses torque for ACT1, scaled so:
•Min ACT1 = -2 x nominal torque
•Max ACT1 = 2 x nominal torque
4 = Power – Uses power for ACT1, scaled so:
•Min ACT1 = -2 x nominal power
•Max ACT1 = 2 x nominal power
4017 ACT2 INPUT
Defines the source for actual value 2 (ACT2).
0 = AI 1 – Uses analog input 1 for ACT2.
1 = AI 2 – Uses analog input 2 for ACT2.
2 = Current – Uses current for ACT2, scaled so:
•Min ACT2 = 0 current
•Max ACT2 = 2 x nominal current
3 = Torque – Uses torque for ACT2, scaled so:
•Min ACT2 = -2 x nominal torque
•Max ACT2 = 2 x nominal torque
4 = Power – Uses power for ACT2, scaled so:
•Min ACT2 = -2 x nominal power
•Max ACT2 = 2 x nominal power
4018 ACT1 MINIMUM
Sets the minimum value for ACT1.
Used with analog input min/max settings (e.g. 1301 MINIMUM AI1,
1302
MAXIMUM AI1).
Scales analog inputs used as actual values.
See figure: A= Normal; B = Inversion (ACT1 MINIMUM > ACT1
MAXIMUM)
4019 ACT1 MAXIMUM
Sets the maximum value for ACT1.
See 4018 ACT1 MINIMUM.
4020 ACT2 MINIMUM
Sets the minimum value for ACT2.
See 4018 ACT1 MINIMUM.
4021 ACT2 MAXIMUM
Sets the maximum value for ACT2.
See 4018 ACT1 MINIMUM.
Code Description
Analog input signal
P 4019
P 4018
P 1301
P 1302
P 1301
P 1302
P 4018
P 4019
ACT1 (%)
Analog input signal
ACT1 (%)
A
B