ACS550 User’s Manual 75
Start-Up
Group 11: Reference Select
This group defines:
How the drive selects between command sources.
Characteristics and sources for REF1 and REF2.
Code Description
1101 KEYPAD REF SEL
Selects the reference controlled in local control mode.
1 = REF1 (Hz/rpm) – Reference type depends on parameter 9904 MOTOR CTRL MODE.
Speed reference (rpm) if 9904 = 1 (VECTOR: SPEED) or 2 (VECTOR: TORQ).
Frequency reference (Hz) if 9904 = 3 (SCALAR: SPEED).
2 = REF2 (%)
1102 EXT1/EXT2 SEL
Defines the source for selecting between the two external control locations EXT1 or EXT2. Thus, defines the source for
Start/Stop/Direction commands and reference signals.
0 = EXT1 – Selects external control location 1 (EXT1).
See parameter 1001 EXT1 COMMANDS for EXT1’s Start/Stop/Dir definitions.
See parameter 1103 REF1 SELECT for EXT1’s reference definitions.
1 = DI1 – Assigns control to EXT1 or EXT2 based on the state of DI1 (DI1 activated = EXT2; DI1 de-activated = EXT1).
2…6 = DI2…DI6 – Assigns control to EXT1 or EXT2 based on the state of the selected digital input. See DI1 above.
7 = EXT2 – Selects external control location 2 (EXT2).
See parameter 1002 EXT2 COMMANDS for EXT2’s Start/Stop/Dir definitions.
See parameter 1106 REF2 SELECT for EXT2’s reference definitions.
8 = COMM – Assigns control of the drive via external control location EXT1 or EXT2 based on the fieldbus control word.
Bit 5 of the Command Word 1 (parameter 0301) defines the active external control location (EXT1 or EXT2).
See Fieldbus user’s manual for detailed instructions.
9 = TIMER FUNCTION 1 – Assigns control to EXT1 or EXT2 based on the state of the Timer Function (Timer Function
activated =
EXT2; Timer Function de-activated = EXT1). See Group 36, Timer Functions.
10…12 = TIMER FUNCTION 2…4 – Assigns control to EXT1 or EXT2 based on the state of the Timer Function. See
Timer Function 1 above.
-1 = DI1(INV) – Assigns control to EXT1 or EXT2 based on the state of DI1 (DI1 activated = EXT1; DI1 de-activated =
EXT2).
-2…-6 = DI2(INV)…DI6(INV) – Assigns control to EXT1 or EXT2 based on the state of the selected digital input. See
DI1(INV) above.
1103 REF1 SELECT
Selects the signal source for external reference REF1.
0 = KEYPAD – Defines the control panel as the reference
source.
1 = AI1 – Defines analog input 1 (AI1) as the reference
source.
2 = AI2 – Defines analog input 2 (AI2) as the reference
source.
3 = AI1/JOYST – Defines analog input 1 (AI1), configured for
joystick operation, as the reference source.
The minimum input signal runs the drive at the maximum
reference in the reverse direction. Define the minimum
using parameter 1104.
The maximum input signal runs the drive at maximum
reference in the forward direction. Define the maximum
using parameter 1105.
Requires parameter 1003=3 (REQUEST).
Warning! Because the low end of the reference range
commands full reverse operation, do not use 0 V as the lower end of the reference range. Doing so means
that if the control signal is lost (which is a 0 V input) the result is full reverse operation. Instead, use the
following set-up so that loss of the analog input triggers a fault, stopping the drive:
Set parameter 1301 MINIMUM AI1 (1304 MINIMUM AI2) at 20% (2 V or 4 mA).
Set parameter 3021 AI1 FAULT LIMIT to a value 5% or higher.
Set parameter 3001 AI<MIN FUNCTION to 1 (FAULT).
4 = AI2/JOYST – Defines analog input 2 (AI2), configured for joystick operation, as the reference source.
See above (AI1/JOYST) description.
+2 %-2 %
10 V /
Hysteresis 4 % of Full Scale
EXT REF 1 MIN
- EXT REF 1 MIN
- EXT REF 1 MAX
EXT
REF 1 MIN
EXT REF 1 MAX
- EXT REF 1 MIN
2V / 4mA
0V / 0mA
20 mA