ACS550 User’s Manual 15
Installation
Power Connection Diagrams
The following diagram shows the terminal layout for frame size R3, which, in
general, applies to frame sizes R1
R6, except for the R5/R6 power and ground
terminals.
Warning! For floating, impedance grounded, or unsymmetrically grounded
networks, disconnect the internal RFI filter by removing:
- On ACS550-01: screws EM1 and EM3.
- On ACS550-U1: screw EM1 (drive is shipped with EM3 already removed).
See "Floating Networks" on page 222.
Panel Connector
Power LED (Green)
Fault LED (Red)
Optional Module 1
J2 – DIP Switch
X1 – Communications
Optional Module 2
GND
Power Output to Motor
Power Input
EM1
X1 – Analog Inputs and Outputs
X1 – Digital Inputs
X1 – Relay Outputs
J2
ON
off position on position
for RS485 Termination
(and 10 V Ref. Voltage Output)
(and 24 V Aux. Voltage Output)
EM3
PE
(U1, V1, W1)
(U2, V2, W2)
Optional braking
Frame
Size
Terminal
Labels
Brake Options
R1, R2 BRK+, BRK- Brake resistor
R3, R4 UDC+, UDC- Braking unit
Chopper and resistor
X0003
(RS485)
R5/R6 differ.
See
Frame Sizes
next page.
Diagram shows the R3 frame.
J2
ON
Other frames have similar layouts.
J1 – DIP Switches for Analog Inputs
J1
AI1: (in Voltage Position)
AI2: (in Current Position)
ON
ON