ACS550 User’s Manual 51
Start-Up
Macro Default Values for Parameters
Parameter default values are listed in "Complete Parameter List for ACS550".
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
Note! There are two sets of values because the defaults are configured for 50 Hz/
IEC compliance (ACS550-01) and 60 Hz/NEMA compliance (ACS550-U1).
ACS550-01
Parameter
ABB
Standard
3-wire
Alternate
Motor
Potentiometer
Hand-auto
PID Control
PFC Control
Torque
Control
9902 APPLIC MACRO 12345678
9904
MOTOR CTRL MODE 31111132
1001 EXT1 COMMANDS 24922112
1002 EXT2 COMMANDS 00007662
1003
DIRECTION 33333113
1102 EXT1/EXT2 SEL 00003233
1103 REF1 SELECT 111121111
1106
REF2 SELECT 2222219192
1201 CONST SPEED SEL 910950904
1304 MINIMUM AI2 0 0 0 020202020
1401
RELAY OUTPUT 1 11111121
1402 RELAY OUTPUT 2 22222232
1403 RELAY OUTPUT 3 333333313
1501
AO1 CONTENT 103 102 102 102 102 102 103 102
1503 AO1 CONTENT MAX 50 50 50 50 50 50 52 50
1507
AO2 CONTENT 104 104 104 104 104 104 130 104
1510 MINIMUM AO2 00000040
1601 RUN ENABLE 00664526
2008
MAXIMUM FREQ 50 50 50 50 50 50 52 50
2201
ACC/DEC 1/2 SEL 50500005
3201
SUPERV 1 PARAM 103 102 102 102 102 102 103 102
3401
SIGNAL 1 PARAM 103 102 102 102 102 102 103 102
4001 GAIN 10 10 10 10 10 10 25 10
4002 INTEGRATION TIME 60 60 60 60 60 60 3 60
4101
GAIN 1111112,51
4102 INTEGRATION TIME 60 60 60 60 60 60 3 60
8123 PFC ENABLE 00000010