170 ACS550 User’s Manual
Embedded Fieldbus
DCU Profile
The following tables describe the CONTROL WORD content for the DCU profile.
7 RESET 0=>1 RESET Fault reset if an active fault exists (Enter
SWITCH-ON INHIBITED). Effective if 1604 =
COMM.
0 OPERATING Continue normal operation
8…9 Unused
10 Unused (
ABB DRV LIM)
REMOTE_CMD
(
ABB DRV FULL)
1 Fieldbus control enabled.
0 CW 0 or Ref 0: Retain last CW and Ref.
CW = 0 and Ref = 0: Fieldbus control
enabled.
Ref and deceleration/acceleration ramp are
locked.
11 EXT CTRL LOC 1
EXT2 SELECT Select external control location 2 (EXT2).
Effective if 1102 =
COMM.
0 EXT1 SELECT Select external control location 1 (EXT1).
Effective if 1102 =
COMM.
12…
15
Unused
DCU Profile
CONTROL WORD (See Parameter 0301)
Bit Name Value Command/Req. Comments
0 STOP 1 Stop Stops according to either the stop mode
parameter or the stop mode requests (bits 7
and 8).
Simultaneous STOP and START commands
result in a stop command.
0 (no op)
1START 1 Start
0 (no op)
2 REVERSE 1 Reverse direction This bit XOR’d with the sign of the reference
defines direction.
0 Forward direction
3 LOCAL 1 Local mode When the fieldbus sets this bit, it steals
control and the drive moves to fieldbus local
control mode.
0 External mode
4 RESET -> 1 Reset Edge sensitive.
other (no op)
5 EXT2 1 Switch to EXT2
0 Switch to EXT1
6 RUN_DISABLE 1 Run disable Inverted run enable.
0 Run enable on
7 STPMODE_R 1 Normal ramp stop
mode
0 (no op)
ABB Drives Profile
CONTROL WORD (See Parameter 5319)
Bit Name Value
Commanded
State
Comments
=
/
=
/