56 ACS550 User’s Manual
Start-Up
1402 RELAY OUTPUT 2045 1 2
1403
RELAY OUTPUT 3045 1 3
1404 RO 1 ON DELAY 0…3600 s 0.1 s 0 s
1405
RO 1 OFF DELAY 0…3600 s 0.1 s 0 s
1406
RO 2 ON DELAY 0…3600 s 0.1 s 0 s
1407 RO 2 OFF DELAY 0…3600 s 0.1 s 0 s
1408
RO 3 ON DELAY 0…3600 s 0.1 s 0 s
1409 RO 3 OFF DELAY 0…3600 s 0.1 s 0 s
1410
RELAY OUTPUT 4045 1 0
1411
RELAY OUTPUT 5045 1 0
1412 RELAY OUTPUT 6045 1 0
1413
RO 4 ON DELAY 0…3600 s 0.1 s 0 s
1414
RO 4 OFF DELAY 0…3600 s 0.1 s 0 s
1415
RO 5 ON DELAY 0…3600 s 0.1 s 0 s
1416
RO 5 OFF DELAY 0…3600 s 0.1 s 0 s
1417
RO 6 ON DELAY 0…3600 s 0.1 s 0 s
1418 RO 6 OFF DELAY 0…3600 s 0.1 s 0 s
Group 15: Analogue Outputs
1501
AO1 CONTENT SEL 99...199 1 103
1502 AO1 CONTENT MIN - - Defined by par. 0103
1503
AO1 CONTENT MAX - - Defined by par. 0103
1504
MINIMUM AO1 0.0…20.0 mA 0.1 mA 0 mA
1505 MAXIMUM AO1 0.0…20.0 mA 0.1 mA 20.0 mA
1506
FILTER AO1 0…10 s 0.1 s 0.1 s
1507
AO2 CONTENT SEL 99…199 1 104
1508 AO2 CONTENT MIN - - Defined by par. 0104
1509
AO2 CONTENT MAX - - Defined by par. 0104
1510
MINIMUM AO2 0.0…20.0 mA 0.1 mA 0 mA
1511 MAXIMUM AO2 0.0…20.0 mA 0.1 mA 20.0 mA
1512
FILTER AO2 0…10 s 0.1 s 0.1 s
Group 16: System Controls
1601
RUN ENABLE 0…7, -1…-6 1 0 9
1602
PARAMETER LOCK 0…2 1 1
1603
PASS CODE 0…65535 1 0
1604
FAULT RESET sEL 0…8, -1…-6 1 0
1605
USER PAR SET CHG 0…6, -1…-6 1 0
1606
LOCAL LOCK 0…8, -1…-6 1 0
1607
PARAM SAVE 0 = DONE, 1 = SAVE 10
1608
START ENABLE 1 0…7, -1…-6 1 0
1609
START ENABLE 2 0…7, -1…-6 1 0
1610
DISPLAY ALARMS 0...1 1 0
Group 20: Limits
2001
MINIMUM SPEED -30000…30000 rpm 1 rpm 0 rpm 9
2002
MAXIMUM SPEED 0…30000 rpm 1 rpm 01: 1500 rpm /
U1: 1800 rpm
9
Code Name Range Resolution Default User S

Table of Contents