60 ACS550 User’s Manual
Start-Up
3419 OUTPUT 3 UNIT -128…127 1 .
3420
OUTPUT 3 MIN -1-
3421 OUTPUT 3 MAX -1-
Group 35: Motor Temp Meas
3501
SENSOR TYPE 0…6 1 0
3502 INPUT SELECTION 1…8 1 1
3503
ALARM LIMIT -10...200 °C / 0...5000 Ohm / 0…1 1 110 °C / 1500 Ohm / 0
3504 FAULT LIMIT -10...200 °C / 0...5000 Ohm / 0…1 1 130 °C / 4000 Ohm / 0
Group 36: Timer Functions
3601
TIMERS ENABLE -6…7 1 0
3602 START TIME 1 00:00:00…23:59:58 2 s 00:00:00
3603
STOP TIME 1 00:00:00…23:59:58 2 s 00:00:00
3604
START DAY 11…7 1 1
3605
STOP DAY 11…7 1 1
3606
START TIME 2 00:00:00…23:59:58 2 s 00:00:00
3607
STOP TIME 2 00:00:00…23:59:58 2 s 00:00:00
3608 START DAY 21…7 1 1
3609
STOP DAY 21…7 1 1
3610
START TIME 3 00:00:00…23:59:58 2 s 00:00:00
3611 STOP TIME 3 00:00:00…23:59:58 2 s 00:00:00
3612
START DAY 31…7 1 1
3613
STOP DAY 31…7 1 1
3614 START TIME 4 00:00:00…23:59:58 2 s 00:00:00
3615
STOP TIME 4 00:00:00…23:59:58 2 s 00:00:00
3616
START DAY 41…7 1 1
3617 STOP DAY 41…7 1 1
3622
BOOSTER SEL -6…6 1 0
3623
BOOSTER TIME 00:00:00…23:59:58 2 s 00:00:00
3624
…
3628
TMR FUNC1…4 SRC 0…31 1 0
Group 40: Process PID Set 1
4001
GAIN 0.1…100 0.1 1.0
4002
INTEGRATION TIME 0.0s = NOT SEL, 0.1…3600 s 0.1 s 60 s
4003
DERIVATION TIME 0…10 s 0.1 s 0 s
4004
PID DERIV FILTER 0…10 s 0.1 s 1 s
4005
ERROR VALUE INV 0 = NO, 1 = YES -0
4006
UNITS 0…31 - 4
4007
UNIT SCALE 0…4 1 1
4008 0%
VALUE Unit and scale defined by par. 4006 and
4007
10.0%
4009 100%
VALUE Unit and scale defined by par. 4006 and
4007
1 100%
4010
SET POINT SEL 0…19 1 1 9
4011
INTERNAL SETPNT Unit and scale defined by par. 4006 and
4007
1 40.0%
Code Name Range Resolution Default User S