ACS550 User’s Manual 63
Start-Up
5202 BAUD RATE 9.6, 19.2, 38.4, 57.6, 115.2 kbits/s - 9.6 kbits/s
5203
PARITY 0 = 8N1, 1 = 8N2, 2 = 8E1, 3 = 8O11 0
5204 OK MESSAGES 0…65535 1 -
5205
PARITY ERRORS 0…65535 1 -
5206
FRAME ERRORS 0…65535 1 -
5207 BUFFER OVERRUNS 0…65535 1 -
5208
CRC ERRORS 0…65535 1 -
Group 53: EFB Protocol
5301
EFB PROTOCOL ID 0...0xFFFF 1 0
5302
EFB STATION ID 0…65535 1 1 9
5303 EFB BAUD RATE 1.2, 2.4, 4.8, … 38.4, 57.6, 76.8 kbits/s - 9.6 kbits/s
5304
EFB PARITY 0 = 8N1, 1 = 8N2, 2 = 8E1, 3 = 8O10
5305
EFB CTRL PROFILE 0 = ABB DRV LIM, 1 = DCU PROFILE,
2 =
ABB DRV FULL
10 (ABB DRV LIM)
5306
EFB OK MESSAGES 0…65535 1 0
5307 EFB CRC ERRORS 0…65535 1 0
5308
EFB UART ERRORS 0…65535 1 0
5309
EFB STATUS 0…65535 1 0 (IDLE)
5310 EFB PAR 10 0…65535 1 0 (NOT SEL)
5311
EFB PAR 11 0…65535 1 0 (NOT SEL)
5312
EFB PAR 12 0…65535 1 0 (NOT SEL)
5313 EFB PAR 13 0…65535 1 0 (NOT SEL)
5314
EFB PAR 14 0…65535 1 0 (NOT SEL)
5315
EFB PAR 15 0…65535 1 0 (NOT SEL)
5316 EFB PAR 16 0…65535 1 0 (NOT SEL)
5317
EFB PAR 17 0…65535 1 0 (NOT SEL)
5318
EFB PAR 18 0...65535 1 0
5319 EFB PAR 19 0...0xFFFF (hex) 1 0
5320
EFB PAR 20 0...0xFFFF (hex) 1 0
Group 81: PFC Control
8103
REFERENCE STEP 1 0.0…100% 0.1% 0%
8104
REFERENCE STEP 2 0.0…100% 0.1% 0%
8105
REFERENCE STEP 3 0.0…100% 0.1% 0%
8109
START FREQ 1 0.0…500 Hz 0.1 Hz 01: 50Hz / U1: 60 Hz
8110
START FREQ 2 0.0…500 Hz 0.1 Hz 01: 50 Hz/ U1: 60 Hz
8111
START FREQ 3 0.0…500 Hz 0.1 Hz 01: 50 Hz/ U1: 60 Hz
8112
LOW FREQ 1 0.0…500 Hz 0.1 Hz 01: 25 Hz/ U1: 30 Hz
8113
LOW FREQ 2 0.0…500 Hz 0.1 Hz 01: 25 Hz/ U1: 30 Hz
8114
LOW FREQ 3 0.0…500 Hz 0.1 Hz 01: 25 Hz/ U1: 30 Hz
8115
AUX MOT START D 0.0…3600 s 0.1 s; 1 s 5 s
8116
AUX MOT STOP D. 0.0…3600 s 0.1 s; 1 s 3 s
8117 NR OF AUX MOT 0…4 1 1 9
8118
AUTOCHNG INTERV 0.0…336 h 0.1 h 0.0 h (NOT SEL) 9
8119
AUTOCHNG LEVEL 0.0…100.0% 0.1% 50%
8120
INTERLOCKS 0…6 1 4 9
Code Name Range Resolution Default User S