174 ACS550-02/U2 User’s Manual
Parameters
Group 32: SUPERVISION
This group defines supervision for up to three signals from Group 01: OPERATING
DATA. Supervision monitors a specified parameter and energizes a relay output if
the parameter passes a defined limit. Use Group 14: RELAY OUTPUTS to define the
relay and whether the relay activates when the signal is too low or too high.
Code Description
3201 SUPERV 1 PARAM
Selects the first supervised parameter.
Must be a parameter number from Group 01: OPERATING
DATA.
•100 =
NOT SELECTED – No parameter selected.
101…159 – Selects parameter 0101…0159.
If the supervised parameter passes a limit, a relay output is
energized.
The supervision limits are defined in this group.
The relay outputs are defined in Group 14: RELAY
OUTPUTS (definition also specifies which supervision limit
is monitored).
LO HI
Operating data supervision using relay outputs, when LOHI.
Case A = Parameter 1401
RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 OVER or SUPRV2 OVER. Use
for monitoring when/if the supervised signal exceeds a
given limit. The relay remains active until the supervised
value drops below the low limit.
Case B = Parameter 1401
RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 UNDER or SUPRV2 UNDER.
Use for monitoring when/if the supervised signal falls
below a given limit. The relay remains active until the
supervised value rises above the high limit.
LO > HI
Operating data supervision using relay outputs, when LO>HI.
The lowest limit (HI 3203) is active initially and remains active
until the supervised parameter goes above the highest limit
(
LO 3202), making that limit the active limit. That limit remains
active until the supervised parameter goes below the lowest
limit (
HI 3203), making that limit active.
Case A = Parameter 1401
RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 OVER or SUPRV2 OVER.
Initially the relay is de-energized. It is energized whenever
the supervised parameter goes above the active limit.
Case B = Parameter 1401
RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is SUPRV1 UNDER or SUPRV2 UNDER.
Initially the relay is energized. It is de-energized whenever
the supervised parameter goes below the active limit.
LO HI
Note: Case LO HI represents a normal hysteresis.
LO > HI
Note: Case LO>HI represents a special hysteresis with
two separate supervision limits.
3202 SUPERV 1 LIM LO
Sets the low limit for the first supervised parameter. See
3201
SUPERV 1 PARAM above.
3203 SUPERV 1 LIM HI
Sets the high limit for the first supervised parameter. See
3201 SUPERV 1 PARAM above.
3204 SUPERV 2 PARAM
Selects the second supervised parameter. See 3201 SUPERV 1 PARAM above.
3205 SUPERV 2 LIM LO
Sets the low limit for the second supervised parameter. See 3204
SUPERV 2 PARAM above.
3206 SUPERV 2 LIM HI
Sets the high limit for the second supervised parameter. See 3204
SUPERV 2 PARAM above.
Value of supervised parameter
Case A
0
Energized (1)
0
HI (3203)
LO (3202)
Case B
Energized (1)
t
t
t
LO (3202)
HI (3203)
Value of supervised parameter
Case A
0
Energized (1)
0
Case B
Energized (1)
Active limit
t
t
t