304 Parameters
35.105 DOL starter status
word
Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as the
source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected control and
feedback sources, and the fault status.
This parameter is read-only.
-
0000b…1111b Status of motor fan control logic. 1 = 1
35.106 DOL starter event
type
Selects the action taken when missing fan feedback is
detected by the motor fan control logic.
Fault
No action No action taken. 0
Warning The drive generates a warning (A781 Motor fan). 1
Fault Drive trips on 71B1 Motor fan.2
36
36 Load analyzer
Peak value and amplitude logger settings.
See also section Load analyzer (page 89).
36.01 PVL signal source Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter 36.02 PVL filter time.
The peak value is stored, along with other pre-selected
signals at the time, into parameters 36.1036.15.
The peak value logger can be reset using parameter 36.09
Reset loggers. The logger is also reset whenever the signal
source is changed. The date and time of the last reset are
stored into parameters 36.16 and 36.17 respectively.
Power inu
out
Zero None (peak value logger disabled). 0
Motor speed used 01.01 Motor speed used (page 117). 1
Output frequency 01.06 Output frequency (page 117). 3
Motor current 01.07 Motor current (page 117). 4
Motor torque 01.10 Motor torque (page 117). 6
DC voltage 01.11 DC voltage (page 117). 7
Power inu out 01.14 Output power (page 118). 8
Speed ref ramp in 23.01 Speed ref ramp input (page 220). 10
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Start command Status of fan control source selected by 35.100.
0 = Stop requested
1 = Start requested
1 Delayed start
command
Fan control bit (delays observed). Select this bit as the source of the
output controlling the fan.
0 = Stopped
1 = Started
2 DOL feedback Status of fan feedback (source selected by 35.103).
0 = Stopped
1 = Running
3 DOL fault (-1) Fault status.
0 = Fault (fan feedback missing). The action taken is selected by
35.106.
1 = No fault
4…15 Reserved