442 Parameters
99.19 Sine filter
capacitance
Defines the capacitance of a custom sine filter, ie. when
parameter 95.15 Special HW settings bit 3 is activated.
If the capacitors are star/wye-connected, enter the
capacitance of one leg
into the parameter.
If the capacitors are delta-connected, multiply the capacitance
of one leg
by 3 and enter the result into the parameter.
Note: For an ABB sine filter (95.15 Special HW settings bit 1),
this parameter is set automatically and should not be
adjusted.
-
0.00 … 100000.00
µF
Capacitance of custom sine filter. 100 = 1 µF
200
200 Safety
FSO-xx settings.
This group contains parameters related to the optional FSO-xx safety functions module. For details, refer to
the documentation of the FSO-xx module.
206
207
208
209
206 I/O bus
configuration
Distributed I/O bus settings.
These groups are only visible with a BCU control unit.
207 I/O bus service
208 I/O bus diagnostics
209 I/O bus fan
identification
These groups contain parameters related to the distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For details, refer to CIO-01 I/O module for distributed I/O
bus control user’s manual (3AXD50000126880 [English]).
No. Name/Value Description Def/FbEq16
M
Sine filter
3~
Drive
C
99.19 = C
C C
M
Sine filter
3~
Drive
CC
C
99.19 = 3 × C