524 Fault tracing
4981 External temperature
1
(Editable message text)
Measured temperature 1 has
exceeded fault limit.
Check the value of parameter 35.02
Measured temperature 1.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of parameter 35.12
Temperature 1 fault limit.
4982 External temperature
2
(Editable message text)
Measured temperature 2 has
exceeded fault limit.
Check the value of parameter 35.03
Measured temperature 2.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of parameter 35.22
Temperature 2 fault limit.
4990 FPTC not found A thermistor protection module
has been activated by
parameter 35.30 but cannot be
detected.
Power down the control unit and make
sure that the module is properly inserted
in the correct slot.
The last digit of the auxiliary code
identifies the slot.
4991 Safe motor
temperature 1
(Editable message text)
The thermistor protection
module installed in slot 1
indicates overtemperature.
Check the cooling of the motor.
Check the motor load and drive ratings.
Check the wiring of the temperature
sensor. Repair wiring if faulty.
Measure the resistance of the sensor.
Replace sensor if faulty.
4992 Safe motor
temperature 2
(Editable message text)
The thermistor protection
module installed in slot 2
indicates overtemperature.
4993 Safe motor
temperature 3
(Editable message text)
The thermistor protection
module installed in slot 3
indicates overtemperature.
5080 Fan
Programmable fault: 31.35
Main fan fault function
Cooling fan feedback missing. See A581 Fan (page 504).
5081 Auxiliary fan not
running
Programmable fault: 31.36
Aux fan fault function
An auxiliary cooling fan
(connected to the fan
connectors on the control unit)
is stuck or disconnected.
See A582 Auxiliary fan not running (page
504).
5090 STO hardware failure Safe torque off hardware
failure.
Contact your local ABB representative,
quoting the auxiliary code. The code
contains location information, especially
with parallel-connected inverter modules.
When converted into a 32-bit binary
number, the bits of the code indicate the
following:
31…28: Number of faulty inverter module
(0…11 decimal). 1111: STO_ACT states
of control unit and inverter modules in
conflict
27: STO_ACT state of inverter modules
26: STO_ACT state of control unit
25: STO1 of control unit
24: STO2 of control unit
23…12: STO1 of inverter modules 12…1
(Bits of non-existing modules set to 1)
11…0: STO2 of inverter modules 12…1
(Bits of non-existing modules set to 1)
Code
(hex)
Fault Cause What to do