A drive with a 12-pulse diode supply unit
Use a three-winding transformer, or two two-winding transformers:
Connection groups: three-winding trasformer: Dy11d0 (or Dd0y1). Two two-winding
transformers: Dy11 and Yy0.
Phase shift between secondaries: 30° electrical
Voltage difference between secondaries: < 0.5%
Short-circuit impedance of secondaries: > 5%
Short-circuit impedance difference between secondaries: Impedance of transformer
windings must be equal, maximum <3% difference of the percentage impedance allowed.
(If short-circuit impedance Zk = 5%, variation can be maximum + 0.15%.)
No grounding of the secondaries
Static shield is recommended.
Two two-winding transformers
~ ~
2
2
3 3
Three-winding transformer
~ ~
2
2
3 3
Two parallel-connected supply units
See the appropriate supplement for the parallel-connected supply units, or contact ABB for
instructions in selecting the transformer(s).
Electrical planning guidelines 19