UL and CSA checklist
WARNING!
Operation of this drive requires detailed installation and operation instructions
provided in the hardware and software manuals. The manuals are provided in
electronic format in the drive package or on the Internet. Keep the manuals with
the drive at all times. Hard copies of the manuals can be ordered through the
manufacturer.
Make sure that the drive type designation label includes the applicable marking.
DANGER - Risk of electric shock. After disconnecting the input power, always wait for
5 minutes to let the intermediate circuit capacitors discharge before you start working on
the drive, motor or motor cable.
The drive is to be used in a heated, indoor controlled environment. The drive must be
installed in clean air according to the enclosure classification. Cooling air must be clean,
free from corrosive materials and electrically conductive dust.
The cables located within the motor circuit must be rated for at least 75 °C in UL-compliant
installations.
The input cable must be protected with fuses or circuit breakers. These protective devices
provide branch circuit protection in accordance with the national regulations (National
Electrical Code (NEC) or Canadian Electrical Code). Obey also any other applicable
local or provincial codes.
WARNING!
The opening of the branch-circuit protective device may be an indication that
a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the device should be examined
and replaced if damaged.
The drive is equipped with UL listed fuses which provide branch circuit protection in
accordance with the National Electrical Code (NEC) and Canadian Electrical Code.
The fuses are listed in the appropriate supply unit hardware manual.
The drive provides motor overload protection. This feature is not enabled when the drives
leaves the ABB factory. For enabling this motor overload protection, see the firmware
manual.
For the drive overvoltage category, see the hardware manuals of the multidrive units.
Approvals
Consult your local ABB representative.
Disclaimers
Generic disclaimer
The manufacturer shall have no obligation with respect to any product which (i) has been
improperly repaired or altered; (ii) has been subjected to misuse, negligence or accident;
(iii) has been used in a manner contrary to the manufacturer’s instructions; or (iv) has failed
as a result of ordinary wear and tear.