• temperature sensor types that you can connect to each option module
• temperature sensor insulation requirement in order to form, together with the insulation
of the option module, a reinforced insulation between the motor live parts and the drive
control unit.
Temperature sensor insulation
requirement
Temperature sensor
type
Option module
Pt100,
Pt1000
KTYPTCInsulation/IsolationType
Reinforced insulationxx-Galvanic isolation between sensor
connector and other connectors (in-
cluding drive control unit connector)
FIO-11
Reinforced insulation-xxGalvanic isolation between sensor
connector and other connectors (in-
cluding drive control unit connector)
FEN-xx
Basic insulation. Connectors of op-
tion module other than sensor con-
nector must be left unconnected.
xxxBasic insulation between sensor
connector and drive control unit
connector. No insulation between
sensor connector and other I/O
connectors.
FAIO-01
No special requirement--xReinforced insulation between
sensor connector and other connect-
ors (including drive control unit con-
nector).
FPTC-
xx
1)
1)
Suitable for use in safety functions (SIL2 / PL c rated).
Implementing a ground fault detection function
■ Cabinet-installed multidrives
The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and motor cable. This function is not a personnel safety
or a fire protection feature. See the firmware manual for more information.
An optional ground fault monitoring device (+Q954) is available for IT (ungrounded) systems.
The option includes a ground fault indicator on the drive cabinet door.
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
Note: As standard, the drive contains capacitors connected between the main circuit and
the frame. These capacitors and long motor cables increase the ground leakage current
and may cause nuisance faults in residual current devices.
■ Multidrives modules
The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and motor cable. This function is not a personnel safety
or a fire protection feature. See the firmware manual for more information.
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
36 Electrical planning guidelines