EasyManua.ls Logo

ABB ACS880 - Page 21

ABB ACS880
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
This table shows the requirements when an ABB motor is in use.
Requirement forNominal AC line
voltage
Motor type
ABB du/dt and common mode filters, insulated
N-end motor bearings
Motor insula-
tion system
P
n
350 kW
or
frame size
IEC 400
100 kW P
n
<
350 kW
or
IEC 315 frame
size < IEC 400
P
n
<
100 kW and
frame size
< IEC 315
P
n
469 hp
or
frame size >
NEMA 580
134 hp P
n
<
469 hp
or
NEMA 500
frame size
NEMA 580
P
n
< 134 hp
and frame
size <
NEMA 500
+ N + CMF+ N-Standard
U
n
500 V
Random-wound M2_,
M3_ and M4_
+ N + du/dt +
CMF
+ N + du/dt+ du/dt
Standard
500 V < U
n
600 V
or
+ N + CMF+ N-Reinforced
+ N + du/dt +
CMF
+ N + du/dt+ du/dt
Reinforced
600 V < U
n
690 V
(cable length
150 m)
+ N + CMF+ N-Reinforced
600 V < U
n
690 V
(cable length >
150 m)
P
n
< 500 kW:
+N + CMF
+ N + CMFn.a.Standard
380 V < U
n
690 V
Form-wound HX_
and AM_
P
n
500 kW:
+N + du/dt + CMF
+ N + du/dt with voltages over 500 V + CMF
Check with the
motor manu-
facturer.
380 V < U
n
690 V
Old
1)
form-wound
HX_ and modular
+ N + CMFEnamelled
wire with fiber
glass taping
0 V < U
n
500 V
Random-wound HX_
and AM_
2)
+ N + du/dt + CMF500 V < U
n
690 V
Consult the motor manufacturer.HDP
1)
manufactured before 1.1.1998
2)
For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
Electrical planning guidelines 21

Table of Contents

Other manuals for ABB ACS880

Related product manuals