AWT420 | UNIVERSAL 4-WIRE, DUAL-INPUT TRANSMITTER | CI/AWT420-EN REV. B
13
pH and conductivity connections
pH/ORP/pIon sensor module connections
NOTICE
ORP (Redox) and Antimony pH sensors do not feature
temperature compensation therefore do not have
temperature sensors or related wiring.
Standard sensors without diagnostic functions
NOTICE
Ensure sensor diagnostics are Off when using standard
sensors without diagnostic functions.
Sensor type RTD wiring
SENSE
1
GUARD
2
REF
3
S.GND
4
RTD 1
5
RTD 2
6
SHIELD
7
RTD 3
8
Clear Black Red White
Blue Black Red White
Clear Black
Red
Red
White
Clear Black White Red Red
Blue Black Red White
Blue Black Red White Grey
Blue Black Red White Yellow
Blue Black Red White Yellow Grey
Standard sensors with diagnostic functions
NOTICE
Ensure sensor diagnostics are On when using standard
sensors with diagnostic functions.
Sensor type RTD wiring
SENSE
1
GUARD
2
REF
3
S.GND
4
RTD 1
5
RTD 2
6
SHIELD
7
RTD 3
8
Blue Yellow Black Green Red White
Clear Red Blue Green/Yellow Red White
Clear Red Blue Green/Yellow Red White Grey