EasyManua.ls Logo

ABB AWT420 - Power Supply Connection

ABB AWT420
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
AWT420 | UNIVERSAL 4-WIRE, DUAL-INPUT TRANSMITTER | CI/AWT420-EN REV. B
…5 Electrical installation
Power supply connection
WARNING
Bodily injuryUSA and Canada only
The use of cable glands, cable/flexible cord for
connection of the mains power source to the mains input
and relay contact output terminals is not permitted.
NOTICE
Electrical installation – ABB recommendations:
Ferrules are fitted to all cables.
Use M4 ring terminals (crimped) on the earth conductor
prior to fitting to the earth stud on the gland plate
(plastic enclosure) or M5 ring terminals prior to fitting
to the earth boss (metal enclosure).
Only 1 cable per cable gland.
Referring to Figure 11, page 15:
1 Using a suitable screwdriver, release door retaining screw
A and open the transmitter door.
2 Release terminal cover retaining screw B and remove
terminal cover plate C.
3 Slide retaining clip D off blanking plug E and remove the
blanking plug if fitted.
4 Fit cable gland F and secure using nut G.
5 Remove gland cover H and route mains power supply
cable I through it.
6 Route the cable through cable gland F and into the
enclosure case.
NOTICE
Use a single-holed bush for the mains power cable.
7 Make connections to the power supply connection
terminals J. Connect earth wire K to earth stud L.
8 Tighten gland cover H.
9 Refit terminal cover C and secure it with retaining screw B.
10 Close the transmitter door and secure with door retaining
screw A.

Table of Contents