ControlMaster CM30 | Universal process controller,
1
/
4
DIN | DS/CM30–EN Rev. L 19
Relays
Number:
4 (1 standard, 3 optional)
Typ e :
Standard with changeover contacts
Optional contacts selectable as NO or NC (by jumper)
Contact ratings:
5 A, 240 V
Update rate:
125 ms
Digital I/O
Number:
6 (2 standard, 4 optional)
Typ e :
User-programmable as input or output
Minimum input pulse duration – 125 ms
Input:
Volt-free or 24 V DC
1-signal 15 to 30 V
—0-signal3 to 5 V
Conforms to IEC 61131-2
Output:
Open collector output
30 V, 100 mA max. switched
Conforms to IEC 61131-2
Update rate:
125 ms
2-Wire transmitter power supply
Number:
2 (1 standard, 1 optional)
Voltage:
—24 V DC
Drive:
2 Loops for each transmitter PSU,
45 mA max.