ControlMaster CMF160
Universal process indicator, fieldmount
12 DS/CMF160–EN Rev. B | ControlMaster CMF160 | Universal process indicator, fieldmount
Custom linearizer*
Number:
—2
Elements:
20 breakpoints
Bank control*
Number of outputs:
—6
Wear levelling:
Rotate or FIFO
Analog inputs
Universal process inputs
Number:
—1 Standard
1 Optional
Type:
Voltage
Current
Resistance (ohms)
—3-Wire RTD
—4-Wire RTD
Thermocouple
Digital volt-free
Digital 24 V
—Frequency
Non-universal process inputs
Number:
—1 Standard
1 Optional
Type:
Voltage
Current
Thermocouple**
Digital volt-free
Digital 24 V
Thermocouple types
B, E, J, K, L, N, R, S, T
Resistance thermometer
Pt100
Other linearizations
x, x
3/2
, x
5/2
, custom linearization
Digital filter
Programmable 0 to 60 s
Display range
–9999 to 99999
Update rate
125 ms
Common mode noise rejection
> 120 dB at 50 / 60 Hz with 300 imbalance resistance
Normal (series) mode noise rejection
> 60 dB at 50 / 60 Hz
CJC rejection ratio
0.05 °C/°C change in ambient temperature
Temperature stability
0.02 %/°C or 2 μV/°C (1 μV/°F)
Long term (input) drift
< 0.1 % of reading or 10 μV annually
Input impedance
> 10 M (mV input)
10 (mA input)
*Functionality level 'Standard' and above only
**Only if universal input 1 on the same input module is configured as 'Thermocouple'