12
Electromagnetic Flowmeter
COPA-XE / MAG-XE
Submenu/Parameter Entry Type Comments
Short Model Number of the flowmeter primary.
Flowmeter Order Number. This number is identical to the one on
the Instrument Tag of the flowmeter primary and on the sticker on
the external EEPROM plugged into the display board.
Flow range for forward and reverse flow directions.
Min. flow range setting 0 - 0.5 m/s
Max. flow range setting 0 - 10 m/s
The flow range end value (0.5 - 10 m/s) is set in this parameter.
The units selection is made in the Submenu Units.
For int. and ext. flow totalization, range 0.001-1000 pulses per
selected flow unit, max. count frequency 5 kHz.
The units selection is made in the Submenu Units.
numeric For external pulse output.
Pulse width can be set between 0.1 ms and 2000 ms.
numeric Range 0-10 % of the flow range setting, applies to the display
indication and all outputs. If the flowrate is below the low flow cut-
off value, the flowrate measurements are stopped.
numeric Range 0.5 - 99.9999 s,
Response time for the current output to reach 99 % of a flowrate
step change
numeric On / off
Standard is off. If the output signal is noisy,
turn filter on and set damping time > 2.4s.
numeric Range 0.01 - 5 g/cm3. For mass flow rate display and totalization
in g, kg, t, uton or pounds.
Zero value display
Manual entry
Valves must be closed. Flowmeter must be full and flow must be
at zero. The automatic zero adjustment is initiated by pressing
ENTER.
Short model no.
DE4
Order no.
9810N1234/A1
Qmax
400.000 m3/h
Pulse
1.0000 /m3
Pulse Width
30.000
Low Flow Cutoff
1.000 %
Damping
10.0000 s
Filter
on
Density
2.54300 g/cm3
System-Zero
3.5 Hz
ENTER
Adjust
manual
Adjust
automatic