3ADW000462R0301 DCS880 Hardware Manual e c
Autotransformer (T3)
The 690 V autotransformer input cannot be used for the field converters DCF803-0016, FEX-425-Int and
DCF803-0035 (maximum isolation voltage is 600 V)
Autotransformer
(T3)
Field current [A] Secondary current
[A]
Weight
[kg]
Power losses
[W]
Fuse F3.2
[A]
U
1
= 500 V 10 %, 50 / 60 Hz
T3, 01 I
F
6 7156510
T3, 02 I
F
12 13 20 100 16
T3, 03 I
F
16 17 20 120 25
T3, 04 I
F
30 33 36 180 50
T3, 05 I
F
50 57 60 250 63
U
1
= 690 V 10 %, 50 / 60 Hz
T3, 11 I
F
6 7 15 80 10
T3, 12 I
F
12 13 20 125 16
T3, 13 I
F
16 17 30 150 20
T3, 14 I
F
30 33 60 230 50
T3, 15 I
F
50 57 60 320 63
Autotransformer
(T3)
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
F
[mm]
Ø G
[mm]
T3, 01 / T3, 11
210 110 112 75 240 10 * 18 95
T3, 02 / T3, 12
T3, 03
210 135 112 101 240 10 * 18 95
T3, 13 230 150 124 118 270 10 * 18 95
T3, 04 260 150 144 123 330 10 * 18 95
T3, 14 / T3, 05
T3, 15
295 175 176 141 380 12 * 18 95
F
A
E
C
B
D
G
ME_TRA_001_T3_b.ai
F3.2 F3.2
T3
T3
S F _ D R O _ 0 0 2 _ T 3 _ a . d s f