Planning the electrical installation
49
3ADW000462R0301 DCS880 Hardware Manual e c
Cross-sectional areas - Tightening torques
Recommended cross-sectional area to DINVDE 0276-1000 and DINVDE 0100-540 (PE) trefoil
arrangement, up to 50°C ambient temperature.
Armature:
Reduced ambient temperature 40°C.
Option for more flexible cable connection available.
You will find instructions on how to calculate the PE conductor’s cross-sectional area in VDE 0100 or
in equivalent national standards. We would remind you that power converters may have a current-
limiting effect.
Excitation:
Converter type C1, D1 U1, V1, W1 PE
[Nm]
I
DC
[A-]
1
[mm²]
(2.)
[mm²]
Iv
[A~]
1
[mm²]
(2.)
[mm²] [mm²]
DCS880-S0B-0025-0d 25 1 x 6 - 21 1 x 4 - 1 x 4 1 x M6 6
DCS880-S0B-0050-0d 50 1 x 10 - 41 1 x 6 - 1 x 6 1 x M6 6
DCS880-S0B-0075-0d 75 1 x 25 - 61 1 x 25 - 1 x 16 1 x M6 6
DCS880-S0B-0100-0d 100 1 x 25 - 82 1 x 25 - 1 x 16 1 x M6 6
DCS880-S0B-0150-0d 150 1 x 35 - 114 1 x 35 - 1 x 16 1 x M10 25
DCS880-S0B-0200-0d 200 2 x 35 1 x 95 163 2 x 25 1 x 95 1 x 25 1 x M10 25
DCS880-S0B-0250-0d 250 2 x 35 1 x 95 204 2 x 25 1 x 95 1 x 25 1 x M10 25
DCS880-S0B-0300-0d 300 2 x 70 1 x 95 220 2 x 50 1 x 95 1 x 50 1 x M10 25
DCS880-S0B-0320-0d 320 2 x 70 1 x 95 220 2 x 50 1 x 95 1 x 50 1 x M10 25
DCS880-S0B-0350-0d 350 2 x 70 - 286 2 x 50 1 x 50 1 x M10 25
DCS880-S0B-0450-0d 450 2 x 95 - 367 2 x 95 - 1 x 50 1 x M10 25
DCS880-S0B-0520-0d 520 2 x 95 - 424 2 x 95 - 1 x 50 1 x M10 25
DCS880-S0B-0650-0d 650 2 x 120 - 555 2 x 120 - 1 x 120 1 x M12 50
DCS880-S0B-0680-0d 680 2 x 120 - 555 2 x 120 - 1 x 120 1 x M12 50
DCS880-S0B-0820-0d 820 2 x 150 - 669 2 x 120 - 1 x 120 1 x M12 50
DCS880-S0B-0900-06/07 900 4 x 95 3 x 150 734 4 x 70 3 x 95 1 x 150 2 x M12 50
DCS880-S0B-1000-0d 1000 2 x 185 - 816 2 x 150 - 1 x 150 1 x M12 50
DCS880-S0B-1190-0d 1190 4 x 120 - 971 4 x 95 3 x 120 1 x 185 2 x M12 50
DCS880-S0B-1200-0d 1200 4 x 120 - 979 4 x 95 3 x 120 1 x 185 2 x M12 50
DCS880-S0B-1500-0d 1500 4 x 185 - 1224 4 x 150 - 2 x 150 2 x M12 50
DCS880-S0B-2000-0d 2000 8 x 120 6 x 185 1632 4 x 240 - 2 x 240 2 x M12 50
DCS880-S0B-1900-0d
1900 8 x 120 6 x 185 1550 4 x 240 3 x 120 4 x M12 50
DCS880-S0B-2050-dd
2050 8 x 120 6 x 185 1673 6 x 120 5 x 150 3 x 120 4 x M12 50
DCS880-S0B-2500-0d
2500 7 x 185 - 2040 8 x 120 6 x 185 4 x 120 4 x M12 50
DCS880-S0B-2600-dd 2600 7 x 185 - 2122 8 x 120 6 x 185 4 x 120 4 x M12 50
DCS880-S0B-3000-0d
3000 8 x 185 - 2448 7 x 185 - 4 x 150 4 x M12 50
DCS880-S0B-3300-dd 3300 8 x 185 - 2693 7 x 185 - 4 x 150 4 x M12 50
DCS880-S0B-4000-dd 4000 7 x 300 - 3264 8 x 240 - 4 x 240 4 x M12 50
DCS880-S0B-4800-0d
4800 8 x 300 - 3876 6 x 300 - 3 x 300 4 x M12 50
DCS880-S0B-5200-0d
5200 8 x 300 - 4202 6 x 300 - 3 x 300 4 x M12 50
Size H1 H1 H2 H3, H5, H6 H4 DCF803-0035
DC output current 6 A 12 A 18 A 25 A 30 A 35 A
max. cross sectional area 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10
min. cross sectional area 1 mm²/ AWG 16 2.5 mm²/ AWG 13 4 mm²/ AWG 11 6 mm²/ AWG 10 6 mm²/ AWG 10 6 mm²/ AWG 10
Tightening torque 1.5 ... 1.7 Nm