Technical data
67
3ADW000462R0301 DCS880 Hardware Manual e c
Regulatory compliance
The converter module and enclosed converter components are designed for use in industrial
environments. In EEA countries, the components fulfil the requirements of the EU directives, see
table below:
Effect of site elevation and ambient temperature on the converter‘s load capacity
Current reduction to % of nominal converter current
European Union Directive
Machinery Directive
Manufacturer's Assurance Harmonized Standards
Converter module
2006/42/EC Declaration of Incorporation EN61800-5-2:2007
EN62061:2005 + Cor.:2010 + A1:2013
+ A2:2015
EN13849-1:2015
EN60204-1:2006 + A1:2009
Low Voltage Directive
2014/35/EU Declaration of Conformity EN61800-5-1:2007
EMC Directive
014/30/EU Declaration of Conformity
(Provided that all installation instructions con-
cerning cable selection, cabling and EMC filters
or dedicated transformer are followed.)
EN61800-3:2004 + A1:2012
RoHS Directive
2011/65/EU Declaration of Conformity
Effect of the site elevation above sea level on the converter’s load capacity
Current reduction to % of nominal converter current
Effect of the ambient temperature on the converter‘s load capacity
Current reduction to % of nominal converter current
Ambient
temperature
Site elevation in m above M.S.L.
1000 m 2000 m 3000 m 4000 m
30°C
100 % 100 % 90 % 80 %
35°C
100 % 95 % 85 % 75 %
40°C
100 % 90 % 80 %
45°C
95 % 85 %
50°C
90 % 80 %
55°C
85 %
50
60
70
80
90
100
1000 2000 3000 4000 5000
m
30
70
80
90
100
110
35 40 45 50
DZ_LIN_017_current-reduction_a.ai
55°C