Questions and Answers

  • G
    George OconnorAug 13, 2025
    What to do if my ABB DPA UPScale ST80 shows an OVERLOAD?
    • S
      Steven AdkinsAug 13, 2025
      If your ABB UPS indicates an overload, it means the load exceeds the UPS's rated power. To resolve this, identify the equipment causing the overload and disconnect it from the UPS. Avoid connecting devices like laser printers, photocopiers, electric heaters, or kettles to the UPS.
  • G
    Gwendolyn FloresAug 16, 2025
    How to troubleshoot MAINS RECT. FAULT on my ABB DPA UPScale ST80?
    • A
      Amanda McleanAug 16, 2025
      If your ABB UPS displays a MAINS RECT. FAULT, it indicates that the mains power supply is outside the prescribed tolerance. This could mean the input power to the UPS is too low or missing. If the site power seems okay, inspect the input circuit breakers and related components that supply power to the UPS.
  • W
    watkinsonAug 20, 2025
    How to troubleshoot MAINS BYP FAULT on my ABB UPS?
    • M
      meagansimonAug 20, 2025
      If your ABB UPS displays a MAINS BYP FAULT, it indicates that the mains power supply is outside the prescribed tolerance. This means the input power to the UPS is either too low or missing. If the site power appears to be functioning correctly, check the input circuit breakers and other components that supply the UPS.
  • D
    David DavisAug 25, 2025
    What to do if my ABB UPS displays OUTPUT SHORT?
    • G
      Glenda HarmonAug 25, 2025
      If your ABB UPS is showing an OUTPUT SHORT error, it means there is a short circuit at the output of the UPS, specifically on the load side. To fix this, check all output connections and repair them as necessary.
  • J
    Jeffrey GainesAug 28, 2025
    What to do if my ABB UPS shows TEMPERATURE HIGH?
    • L
      lisaturnerAug 28, 2025
      If your ABB UPS displays a TEMPERATURE HIGH warning, it means the UPS temperature has exceeded the allowed value. First, check that the ambient temperature around the UPS is less than 40° C.
  • F
    Felicia ReyesSep 1, 2025
    What does SYNCHRON. FAULT mean on my ABB DPA UPScale ST80?
    • R
      rhonda78Sep 1, 2025
      SYNCHRON. FAULT on your ABB UPS means that the inverter and mains are not synchronized. This indicates that the frequency of the input voltage to the UPS is outside operational limits, and the UPS static bypass has been temporarily disabled.
  • K
    Kurt HendersonSep 4, 2025
    What to do if my ABB DPA UPScale ST80 UPS says BATTERY IN DISCHARGE?
    • J
      Joy PooleSep 4, 2025
      If your ABB UPS indicates BATTERY IN DISCHARGE, it means the battery is near the end of its autonomy. To prevent data loss or damage, shut down the load connected to the UPS before the UPS automatically switches off to protect its batteries.
  • S
    Stephanie BrownSep 8, 2025
    What does MANUAL BYP IS CLOSED mean on my ABB DPA UPScale ST80 UPS?
    • K
      Kara McfarlandSep 8, 2025
      If your ABB UPS displays MANUAL BYP IS CLOSED, it indicates that the UPS is currently on maintenance bypass.