Operating manual
Conceptpower DPA 500
100-500 kW

Table of Contents

Other manuals for ABB Conceptpower DPA 500

Questions and Answers

  • S
    schneidernatashaAug 13, 2025
    What to do if my ABB Conceptpower DPA 500 shows an OVERLOAD?
    • A
      Anna BradyAug 13, 2025
      If your ABB UPS indicates an overload, it means the connected load exceeds the UPS's rated power. Identify and disconnect the equipment causing the overload. Avoid connecting devices like laser printers, photocopiers, electric heaters, or kettles to the UPS.
  • R
    Regina GarciaAug 17, 2025
    How to resolve MAINS RECT. FAULT on my ABB UPS?
    • D
      Douglas MaysAug 17, 2025
      A 'MAINS RECT. FAULT' on your ABB UPS indicates that the input power is either too low or missing. If the site power seems fine, inspect the input circuit breakers supplying the UPS.
  • J
    jonathanmorenoAug 21, 2025
    How to resolve MAINS BYP FAULT on my ABB UPS?
    • M
      Mark PerezAug 21, 2025
      A 'MAINS BYP FAULT' on your ABB UPS means the input power is too low or missing. If the site power appears OK, check the input circuit breakers supplying the UPS.
  • J
    Joshua MorganAug 25, 2025
    What to do if my ABB Conceptpower DPA 500 UPS displays OUTPUT SHORT?
    • S
      Steven ThomasAug 26, 2025
      If your ABB UPS is showing 'OUTPUT SHORT', it indicates a short circuit at the output of the UPS on the load side. You should inspect all output connections and repair them as necessary.
  • K
    Kevin SuttonAug 28, 2025
    What to do if my ABB Conceptpower DPA 500 shows TEMPERATURE HIGH?
    • D
      danielle26Aug 29, 2025
      If your ABB UPS displays 'TEMPERATURE HIGH', it means the UPS temperature has exceeded the allowed value. Ensure the ambient temperature around the UPS is below 40° C.
  • J
    jessica48Sep 1, 2025
    What to do if my ABB UPS displays BATTERY IN DISCHARGE?
    • A
      Amy AndersonSep 1, 2025
      If your ABB UPS shows 'BATTERY IN DISCHARGE', the battery is nearing the end of its autonomy. To protect the batteries, shut down the load connected to the UPS before it automatically switches off.
  • A
    alexisgarciaSep 4, 2025
    What causes SYNCHRON. FAULT in ABB Conceptpower DPA 500 UPS?
    • S
      sharpkellySep 4, 2025
      A 'SYNCHRON. FAULT' in your ABB UPS occurs when the frequency of the input voltage to the UPS is outside operational limits, causing the UPS static bypass to be temporarily disabled.
  • R
    Richard WheelerSep 8, 2025
    Why does my ABB Conceptpower DPA 500 show MANUAL BYP IS CLOSED?
    • J
      Jessica LiuSep 8, 2025
      This alarm is only displayed if the UPS is on Maintenance Bypass.

Summary

Safety Instructions

General Safety Precautions

Adherence to manual instructions and precautions for safe operation and avoiding injury.

Electrical Hazard Warnings

Prohibits removing screws, emphasizes PE connection, and warns about dangerous voltages.

UPS System Characteristics

Installation and Wiring

Electrical Installation Requirements

Outlines requirements for qualified personnel, wiring, fuse protection, and power connections.

AC Wiring Instructions

Step-by-step guide for connecting AC power, including PE, single/dual input feeds, and output wiring.

DC Wiring Instructions

Procedures for connecting DC battery wiring, including common and separate battery configurations.

UPS Operation

Commissioning Process

Outlines the steps for commissioning the UPS by trained service engineers.

Start-up Procedure

Step-by-step guide for safely starting up the UPS system, including checks and panel displays.

Shutdown Procedure

Procedures for completely shutting down the UPS system, ensuring safety and load disconnection.

UPS Module Replacement

Detailed procedures for extracting and fitting UPS modules, including safety precautions.

Maintenance and Troubleshooting

Troubleshooting Faults

Common Faults and Solutions

Lists major alarm conditions, their meanings, and suggested solutions for troubleshooting.

ABB Conceptpower DPA 500 Specifications

General IconGeneral
Power Rating500 kVA
Frequency50/60 Hz
EfficiencyUp to 96%
TopologyDouble Conversion Online
Operating Temperature0 to 40 °C
Humidity0 to 95% (non-condensing)
Input Voltage400 V
Output Voltage400 V
Battery TypeValve-regulated lead-acid (VRLA)
Communication InterfaceRS-232, USB
DimensionsVaries depending on configuration; consult product documentation
WeightVaries depending on configuration
ScalabilityModular, scalable