6.4.3 Start up and installation
When the UPS is energized, the display is automatically turned on. It is initiated for a few seconds and
subsequently the user is directed to the mimic diagram screen.
6.4.4 Navigation
A few icons and some information are displayed in the top of every screen as indicated in the Figure
18.
Figure 18: Display header
A
Home
Directs the user to the navigation screen.
B
Mimic diagram
Directs the user to the mimic diagram screen.
C
Xtra VFI
The Extra VFI button is accessible from all screens and
functions as toggle to switch between
Xtra VFI measures
screen and
Xtra VFI status bar
screen.
D
Warning symbol
Appears in case of alarms or events. Touching this icon the
alarm is silenced and directs to the
Event log
screen.
E
Date
-
F
Time
-
G
Module selection
Directs the user to the module selection screen from where
it is possible to select the module and start the navigation
(status and measurements) on module level.
H
System status
System status: indicates that the user is in the system level
navigation.
I
UPS number
The numbering after the symbol „P” is sequential and
represents each module or frame in the system. For eg.
“P01” indicates the UPS number 01 in a parallel system.
Defining the UPS positioning in a system:
The position of each UPS within a system has to be configured not only in the graphical interface but
also in the hardware. The position is determined as one of the following:
“First” UPS in the parallel configuration
“Middle” UPS in the parallel configuration (there may be more than one)
“Last” UPS in the parallel configuration. The maximum number of parallel cabinets is six (6). The
maximum number of parallel modules is thirty (30).
In a multi-cabinet configuration chain, the cabinet is seen as “First” and “Last” in an imaginary chain.
Configure the DIP switch for the existing system. For more details concerning the positions of this DIP
switch, refer to Chapter 6.2.3
.
H
I
A
B
D
E
F
G
C