6.2.4 Multidrop Configuration
Multidrop cable connection
Insert the splitter/s supplied with the installation inside the Multidrop connector/s
JR2 on NW22085 on all middle unit/s.
Connect the “
” end of the multidrop cable on the First Unit and the
“
” end on the second Unit (If more than two unit inside the splitter).
Proceed on the same way with all other unit on the installation as shown on the
picture.
Board NW22085 Jumper & Switches configuration
Verify that the customer interface board (NW22085) of each unit correctly configured according to the
following table
JUMPER JP 2 on PCB NW22085D (with ROM76-12) or NW22085E or later versions
First unit OFF
Middle Unit ON
Last Unit ON
on the (older) versions NW22085
without ROM76-12 make a bridge between X3-11 & X3-12.
6.2.5 ON/OFF – Main Buttons
The ON/OFF-Buttons serve to shutdown the UPS-system for service or maintenance or for
emergency reasons.
WHEN BOTH ON/OFF BUTTONS ON ALL UPS MODULES IN A PARALLEL
SYSTEM ARE PUSHED THE POWER SUPPLY TO THE LOAD WILL BE
INTERRUPTED