Modifications reserved
1.4 Key Features of Conceptpower DPA 500
• Xtra VFI double conversion mode
• 100 kW rated power module / 500 kW rated power in single frame
• Extended power range: from 100 kW to 3 MW
• Unity output power factor (kVA = kW)
• Double conversion efficiency up to 96 %
• Efficiency in eco-mode ≥ 99 %
• Online Swap Modularity (OSM)
• Online serviceability
• Top or bottom cable entry (standard)
• Built-in back-feed protection (standard)
• Graphical display on system level
• DPA displays in each module
This Technical Datasheet (TDS) provides all technical specification required by IEC 62040-3, providing
mechanical, electrical and environmental characteristics. It can be used for tendering and end-user
requirements. CONCEPTPOWER DPA 500 is designed to respond to the actual UPS standards which
are:
• Safety, IEC / EN 62040-1
• EMC, IEC / EN 62040-2
• Performance, IEC / EN 62040-3