Modifications reserved
2 General characteristics
Conceptpower DPA 500 Values Unit
Photograph
(front view)
Power, rated:
Apparent
500
kVA
Active
500
kW
Power, range
100 – 3000
kW
UPS type: on-line, trasformerfree, decentralized parallel architecture
Parallel capability: up to 6 frames
Battery: not included
Performance classification: VFI-SS-111
MECHANICAL
Dimensions (width×height×depth)
1580x1975x940
mm
Mass, approx. (500kW system, with 5 modules)
975
kg
Acoustic noise (acc. to IEC 62040-3)
in normal mode (at <=25°C) at 100% / 50% Load
75 / 67 dBA
in battery mode (at <=25°C) at 100% / 50% Load
73 / 66 dBA
SAFETY
Access: operator/restricted
Degree of protection against hazards and water ingress: IP 20
ELECTROMAGNETIC COMPATIBILITY
Compliant to IEC/EN 62040-2
Category Emission / Immunity
C3 / C3
ENVIRONMENTAL
Storage temperature range
°C
Operative temperature range
°C
Relative humidity
%
Max. altitude without de-rating
m