2.6 Multiple cabinet configuration
Multiple cabinet configuration is possible up to 6 frames (30 modules) in parallel. The system is
flexible: each frame can be equipped with 1-5 modules at customer choice.
Multiple cabinet system requires:
• at least two UPS cabinets with at least 1 module each
• each cabinet to be equipped with the parallel kit
• one parallel cable and one Multidrop cable connect that connect two frames
The start-up of a multiple cabinet systems is an operation which can be performed by a service
engineer form the manufacturer or by a service engineer from an agent certified by the manufacturer.
Please refer to the service manual to perform this operation.
power connection
parallel cable
Multidrop cable (carries the graphical display information)
Figure 2: Maximum multiple cabinet configuration; 6 frames, 30 modules.