General characteristics
2.1 Environmental requirements
To operate the UPS at the best efficiency point, your installation site should meet the environmental
parameters outlined in this manual. Excessive amount of dust or moisture in the operating
environment may cause damage or lead to malfunction. The UPS should be always protected from
the outside weather and sunshine. The operating environment must meet the weight, airflow, size and
clearance requirements specified in the attached “technical datasheet” of this manual or in the
technical datasheet of the same product (separate document).
Under no circumstances, the UPS should be installed in an airtight room, in the presence of
flammable gases, or in an environment, exceeding environmental requirements specified here below.
The ambient temperature for operating the UPS must be in the range 0 °C to +40 °C. The Ideal
temperature also recommended to achieve a long life of the UPS and VRLA batteries is +20°C to
+25°C. The relative humidity should be below 95% (non-condensing) and the max. altitude without
de-rating is 1000m above sea level.
2.2 CE marking and declaration of safety and EMC conformity
The product has the CE marking in compliance with the following European directives
Low Voltage Directive: 2014/35/EU
EMC Directive: 2014/30/EU
The product applies the actual UPS standards, listed in the Table 1 below.
Table 1: UPS Standards.
Description Product standards General standards
Safety
IEC/EN 62040-1
IEC/EN 60950-1
Electromagnetic Compatibility (EMC) IEC/EN 62040-2
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-2-2
2.3 Inquiries
Address inquiries about the UPS to the local office or agent certified by the supplier. Please note the
type code and the serial number shown in the type plate of the product (see chapter 2.4
) of the
equipment and contact your nearest agent certified by the supplier.