Modifications reserved
5.2 Customer interface and DRY PORTs (volt-free contacts)
All Terminals X1-X3 can hold Cable from 0.2mm2 – 1.5mm2
X1 is a 230VAC output which allows to interface with a interlock system.
All X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A
All X3 (except X3 5/6 which is a 12VDC source) are inputs, cable max. R 50Ω at 20mA
Table 10: Customer Interface Conceptpower DPA 500
X3
X3 / 14
GND
-
(only the optional battery sensor from
ABB is compatible)
X3 / 13 +3.3VDC
-
X3 / 12
GND
GENERATOR_
OPER_ON
Generator Operation
(N.O.) Min. contact load 12V / 1mA
X3 / 11 +12Vdc
X3 / 10
GND
PARRALEL_SW_OPEN
PARRALEL_SW_CLOSE
External Output Breaker
(N.O.) Min. contact load 12V / 20mA.
X3 / 9 +12Vdc
X3 / 8
GND
EXT_MAN_BYP
External Manual Bypass (Ext.
IA1)
(N.O.) Min. contact load 20mA
X3 / 7 +12Vdc
X3 / 6
+12Vdc
-
protected)
(Max. 200mA)
X3 / 5 GND
-
X3 / 4
GND
REMOTE_
SHUTDOWN-
RSD (Remote Shut down)
Default setting: disabled. Possibility to
enable and set NO or NC via NewSet.
X3 / 3 +12Vdc
X3 / 2
-
REMOTE_
SHUTDOWN-
RSD (Remote Shut down ) for
external switch
Max. 250Vac/8A ;30Vdc/8A
;110Vdc/0.3A ;220Vdc/0.12A
X3 / 1 -
X2
X2 / 18
-
-
Common
X2 / 17 -
-
Relais AUX
(function on request, to be defined)
X2 / 16 -
-
X2 / 15
COMMON_ALARM
X2 / 14 ALARM
No Alarm Condition
X2 / 13
Common Alarm (System)
X2 / 12
LOAD_ON_MAINS
Common
X2 / 11 Message
No Load on Bypass
X2 / 10
Load On Bypass (Mains)
X2 / 9
BATT_LOW
Common
X2 / 8 ALARM
Battery Ok
X2 / 7
Battery Low
X2 / 6
LOAD_ON_INV
Common
X2 / 5 Message
No Load on Inverter
X2 / 4
Load on Inverter
X2 / 3
MAINS_OK
Common
X2 / 2 ALARM
Mains Failure
X2 / 1
Mains Present
X1
X1 / 2
EXT_MAN_BYP
Interlock Function
Max. 30Vdc/2A; 60Vdc/0.7A
(Ext Manual Bypass) / 2AT
X1 / 1