Information for use in USA / Canada
Applications according to NFPA 79
Only suitable for use in a limited voltage / current circuitry.
The limited voltage / current source must comply with one of the
following:
a) An isolating device such that the maximum open circuit voltage
potential available to the circuit is not more than +24 VDC and
the current is limited to a value not exceeding 8 A measured after
1 min of operation.
or
b) A suitable isolating source in conjunction with a fuse in
accordance with UL248. The fuse shall be rated max. 4 A and be
installed in the +24 VDC power supply to the device in order to
limit the available current.
Any listed (CYJV/7), M12, 4-pin or 5-pin, A-coding mating connector. Cord
provided shall be 24 AWG (0.2 mm
2
) minimum when one end is provided
with leads for connection to the source, 30 AWG (0.05 mm
2
) minimum
when connectors are provided on both ends.
Maximum ampere ratings of the overcurrent protection:
Safety / Harmonized Standards
Type 4, high level coded, (Eva Unique code)
Type 4, low level coded, (Eva General code)