26 EN – R6…R9 Quick installation guide
R0-
R4
R6-
R9
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
For information on reforming the capacitors, see Converter module capacitor
reforming instructions (3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents
.
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Ensure the cooling
See table ?1 on page 5 (UL: table ?2 on page 5) for the losses. The allowed operating
temperature range of the drive is -15 to +50 °C (+5 to +122 °F). No condensation or
frost is allowed. For more information on the ambient temperature and derating, see
chapter Technical data in ACS580-01 (0.75 to 250 kW) hardware manual
(3AXD50000018826 [English]).
Protect the drive and input power cable
See tables ?3, IV and ?5 on pages 6 and 6 for the fuses.
If you use gG fuses, make sure that the operating time of the fuse is below 0.5 seconds.
Follow the local regulations.
Install the drive on the wall
Warning! The drive module is heavy (42 to 103 kg / 93 to 227 lb). Use a
suitable lifting device. Do not lift the module manually. Make sure that the wall
and the fixing devices can carry the weight.
See figure R6…R9 Figures A on page 45.